Skip to main navigation Skip to search Skip to main content

Chilled ceiling and displacement ventilation aided with personalized evaporative cooler

  • W. Chakroun*
  • , N. Ghaddar
  • , K. Ghali
  • *Corresponding author for this work
  • Department of Mechanical Engineering
  • American University of Beirut

Research output: Contribution to journal › Article › peer-review

65 Scopus citations

Abstract

This paper aims at studying the energy impact of a chilled ceiling displacement ventilation CC/DV system aided with a personalized evaporative cooler (PEC) directed towards the occupant trunk and face. A simulation model is developed for integrating the personalized cooler with the ascending thermal plume. The thermal model of the conditioned room air around the person is integrated with a segmental bioheat and thermal comfort model to predict the human thermal comfort. The model is validated with experimental data on the vertical temperature distribution in the room, and the recorded overall comfort perceived by surveyed subjects. Experimental results agreed well with predicted values of temperature and comfort level. When using personalized cooling, the DV supply air temperature can be as high as 24 °C while the PEC at flow rates of 3-10 l/s achieved similar comfort with a DV system at supply temperature of 21 °C. At equal thermal comfort level, the integrated CC/DV system, PEC model resulted in up to 17.5% energy savings compared to the CC/DV system without a PEC. When mixed air is used in the CC/DV system additional 25% savings in energy is realized when compared with energy used for the 100% fresh air without the PEC.

Original languageEnglish
Pages (from-to)3250-3257
Number of pages8
JournalEnergy and Buildings
Volume43
Issue number11
DOIs
StatePublished - Nov 2011

UN SDGs

This output contributes to the following UN Sustainable Development Goals (SDGs)

  1. SDG 7 - Affordable and Clean Energy
    SDG 7 Affordable and Clean Energy

Keywords

  • Displacement ventilation
  • Mixed air in displacement ventilation system
  • Personalized evaporative cooler
  • Thermal comfort

Fingerprint

Dive into the research topics of 'Chilled ceiling and displacement ventilation aided with personalized evaporative cooler'. Together they form a unique fingerprint.

Cite this