Effect of size on ground-coupled heat pump performance

  • M. Alalaimi
  • , S. Lorente
  • , R. Anderson
  • , A. Bejan*
  • *Corresponding author for this work
  • Duke University
  • Université de Toulouse, UPS, LMDC (Laboratoire Matériaux et Durabilité des Constructions)
  • National Renewable Energy Laboratory

Research output: Contribution to journal › Article › peer-review

16 Scopus citations

Abstract

Here we document and explain interactions between two thermodynamic trends that determine the optimum performance of refrigeration and heat pump systems. We show analytically why the performance of the system must increase with the size of the installation. The second law efficiency of heat pump systems must increase with their size. We also show that the power requirement for a specific ground-coupled heat pump system must decrease as the size of the ground heat exchanger increases. From these two trends emerges the tradeoff between the size of the heat pump and the size of the ground heat exchanger. The challenge is to find the optimum size of the ground-coupled heat pump. We show numerically the optimum heat pump size and the ground heat exchanger size that correspond to minimum total power requirement subject to a cost constraint.

Original languageEnglish
Pages (from-to)115-121
Number of pages7
JournalInternational Journal of Heat and Mass Transfer
Volume64
DOIs
StatePublished - 2013
Externally publishedYes

UN SDGs

This output contributes to the following UN Sustainable Development Goals (SDGs)

  1. SDG 7 - Affordable and Clean Energy
    SDG 7 Affordable and Clean Energy

Keywords

  • Constructal design
  • Cooling
  • Ground heat exchangers
  • Heat pumps

Fingerprint

Dive into the research topics of 'Effect of size on ground-coupled heat pump performance'. Together they form a unique fingerprint.

Cite this