Abstract
This paper presents the effect of tube-tape clearance on the heat transfer for a fully developed turbulent flow in an isothermal tube. Tests were performed on 15 different tapes; they include 3 twisted tape ratios each with five different widths. Results have demonstrated that as the tube-tape clearance decreases, the heat transfer enhancement increases. For the case of twist ratio of 3.6, the tape widths have resulted in almost 17% difference in the enhancement. On the other hand, for the cases of twist ratios of 5.4 and 7.1, the enhancements were 9% and 4%, respectively. For practical design of thermal systems, operating under turbulent flow condition, small twist ratio and tight-fit tape are desirable in order to obtain a reasonably high heat transfer enhancement. The heat transfer for twist ratio of 3.6 and loose-fit tape shows nearly the same enhancement as the case of the tight-fit tape for the same twist ratio. Such behavior indicates the presence of an optimum tape width, and such width is a function of the twist ratio and Reynolds number.
| Original language | English |
|---|---|
| Pages (from-to) | 173-178 |
| Number of pages | 6 |
| Journal | International Journal of Heat and Fluid Flow |
| Volume | 17 |
| Issue number | 2 |
| DOIs | |
| State | Published - Apr 1996 |
Fingerprint
Dive into the research topics of 'Effect of tube-tape clearance on heat transfer for fully developed turbulent flow in a horizontal isothermal tube'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver